PAP Mini Light Duty Series

Air Cooled

Built-in Intelligent Monitor

Easy to use function keys for expanded functionality

  • F001 Automatic recovery after power outage
  • F002 RUN/STOP control selection
  • F003 Alarm signal output select
  • F099 Settings lock
  • F100 Controlled outlet air temperature warning

Specification table

Model PAP01B (temperature control type) PAP01B-KJ (temperature and humidity control type)
Performance
Specifications
Setting temperature / humidity range (1) °C,% 18 - 30 18 to 30, 45 to 75
Temperature / humidity control accuracy (2) °C,% ± 0.1 ± 0.1, ± 1.0
Cooling + heating capacity (50/60 Hz) (3) kW 0.33 / 0.39 0.77 / 0.84
(Maximum cooling capacity) (kW) (0.22 / 0.26) (0.37 / 0.44)
Rated treatment volume m3/min 0.7 to 1.0
Maximum external static pressure (4) Pa 120/130 120/160
Environmental
Conditions
Ambient temperature and humidity range (suction air) (1) °C,% 15 to 35, 30 to 70
Suction temperature change gradient °C/h Within ± 1
Suction humidity change gradient %/H Within ± 5
External dimensions (height × depth × width) (5) mm 346 × 500 × 412 765 × 620 × 390
Product weight kg (32) (69)
Control air outlet mm φ75 φ100
Humidification
Water
Water quality - Pure water (electric conductivity 1 to 10 μS / cm)
Maximum humidification capacity (6) kg/h - 0.8
Supply temperature range °C - 10 to 40
Connection port diameter - Rc 1/4
Power
Specifications
Power supply (7) (11) V(Hz) Single phase 100 ± 10% (50/60)
Power consumption kW 0.32 / 0.34 1.2 / 1.2
Current (8) A 4.0 / 3.9 13/13
Power supply capacity (9) kVA 0.34 / 0.38 1.5 / 1.5
Noise value (50/60 Hz) (10) dB 54/56 58/60
Refrigerant R134a R407C
Refrigerating compressor output kW 0.25 0.3
  1. It does not represent controllable temperature and humidity range. The controllable temperature and humidity range varies depending on the suction air temperature humidity and the treatment air volume. Please set processing air volume according to usage environment.
  2. When suction air temperature and humidity are stable. One discharge port. Controller display value accuracy. Rated maximum air volume.
  3. Inhalation (ambient) Air temperature Temperature and humidity 30°C 70%, treatment volume 3m3/min.
  4. External static pressure when throttled at the control air discharge side on the outlet side of the blower, and operated at the maximum rated processing air volume.
  5. The height includes the discharge port.
  6. Maximum humidification operation within specification range.
  7. To prevent voltage drop, please install a special socket outlet.
  8. Maximum value within specification range.
  9. Maximum operation current within specified range.
  10. By attaching a muffler duct, it is possible to lower the noise value.
  11. Power cord 2 m (receptacle specification) included.

Always use insulation ducts as connecting ducts and shorten them as much as possible. (Recommended within 3m)

Model PAP03C (temperature control type) PAP03C-KJ (temperature and humidity control type)
Performance
Specifications
Setting temperature / humidity range (1) °C,% 18 - 30 18 to 30, 45 to 75
Temperature / humidity control accuracy (2) °C,% ±0.1 ±0.1,±1.0
Cooling + heating capacity (50/60 Hz) (3) kW 1.65/1.85 1.8/2.12
(Maximum cooling capacity) (kW) (1.15/1.35) (1.2/1.42)
Rated processing volume (1) m3/min 2.0 to 4.0
Maximum external static pressure (4) Pa 110/150 110/150
Environmental
Conditions
Ambient temperature and humidity range (suction air) (1)(5) °C,% 15 to 40, 30 to 70
Suction temperature change gradient °C/h Within ± 1
Suction humidity change gradient %/H Within ± 5
External dimensions (height × depth × width) (6) mm 1070 × 590 × 480 1350 × 680 × 520
Product weight kg (95) (135)
Control air outlet mm φ 98
Humidification
Water
Water quality - Pure water (electrical conductivity 0.1 to 10 µS / cm)
Maximum humidification capacity (7) kg/h - 2.3
Supply temperature range °C - 10 to 40
Connection port diameter - Rc 1/4
Power
Specifications
Power supply (8) V (Hz) Three phases 200 ± 10% (50/60)
Power consumption (9) kW 0.75 / 0.85 2.7 / 3.1
Current (10) A 3.8 / 3.8 11/12
Power supply capacity (11) kVA 1.4 4.0
Noise value (50/60 Hz) dB 64/65 65/66
Refrigerant R410A
Refrigerating compressor output kW 0.8 0.85
  1. It does not represent controllable temperature and humidity range. The controllable temperature and humidity range varies depending on the suction air temperature humidity and the treatment air volume. Please set processing air volume according to usage environment.
  2. When suction air temperature and humidity are stable. Ejection port 1 point, accuracy of controller display value. At the rated treatment air volume (3m3/min). Temperature temporarily fluctuates due to refrigerating machine oil return operation for about 2 minutes after starting operation. Also, if the target humidity is high, the above precision may not be maintained at the timing of humidification water supply. In that case, you can reduce fluctuation by adjusting the water supply related parameters.
  3. Inhalation (ambient) Air temperature Temperature and humidity 30 °C 70%, treatment volume 3m3/min.
  4. When the treatment air volume is 3m3/min.
  5. For details of usable ambient temperature and humidity range.
  6. The height includes the discharge port.
  7. Maximum humidification operation within the operating range.
  8. The interphase balance of the power supply voltage should be within ± 3%.
  9. Suction (ambient) Air temperature Temperature Humidity 30 °C 70%, Treatment air volume 3m3/min, Power supply voltage AC 200V.
  10. Maximum value within specification range.
  11. Maximum operation current within specified range.

Always use insulation ducts as connecting ducts and shorten them as much as possible. (Recommended within 3m)

External Dimentions