ORION® RKE Series Chillers

Built-in Water Tank

Built-in Water Tank

Energy-Saving Chiller DC Inverter Chiller - Air Cooled Series

Refrigeration Equipment

Cooling Capacity: 2.7KW - 8.7 KW

Built-in Water Tank

Energy-Saving Chiller DC Inverter Chiller - Water Cooled Series

Refrigeration Equipment

Cooling Capacity: 2.7KW - 8.7 KW

Specifications Chart

Item - Model RKE750A1-V-G1
RKE750A1-V-G2 (w/casters)
RKE1500B1-V-G1
RKE1500B1-V-G2 (w/casters)
RKE2200B1-V-G1
RKE2200B1-V-G2 (w/casters)
RKE1500B1-VW-G1
RKE1500B1-VW-G2 (w/casters)
RKE2200B1-VW-G1
RKE1500B1-VW-G2 (w/casters)
Performance Specifications
Cooling Capacity Room Temp. 32°C, Set Temp. 20°C 1 kW 2.7 5.3 8.7 6.0
(Chiller water temp: 20 °C)
10.4
(Chilled water temp: 20°C)
Room Temp. 25°C, Set Temp. 20°C kW 2.9 5.8 9.5
Ambient Temp. range °C –5 ~ 43 2 ~ 43
Operating Temp. Range
(Liquid Temp.)
°C 5 ~ 35 5 ~ 35
Control Precision (4) °C ± 0.1°C (Under stable load, ambient temperature and power source) ± 0.1 (Under stable load, ambient temperature and power source,)
± 0.5°C (When the current load is continuously within ± 10%) ± 0.5 (When the current load is continuously within ± 10%)
Minimum operating
circulation rate (50/60Hz)
L/min 10 (head: 20/30m) 12/21 (head: 50m) 28/43 (head: 50m) 12/21 (head: 50m) 28/43 (head: 50m)
Power Specifications
Power Source (2) V (Hz) Three phase 200 ± 10% (50/60) , 220 ± 10% (60) Three phase 200 ± 10% (50/60) , 220 ± 10% (60)
Power consumption (1) kW 1.2/1.3 1.3 2.3/2.4 2.4 4.6/4.7 4.7 1.7/1.8 1.8 3.5/3.7 3.7
Electric current (1) A 4.5,5.3 4.7 8.7/9.0 9.0 16/17 17 6.5,7.1 6.6 14/14 14
Power capacity (3) kVA 2.1 4.2 6.5 3 5.5
Breaker capacity A 10 (With heater installed: 15)
Current sensitivity current 30mA High-speed
15 (With heater installed: 20)
Current sensitivity current 30mA High-speed
30 6 15 (With heater installed: 20)
Current sensitivity: 30mA High-speed
30 6
Operation Control method Compressor speed control Compressor Speed Control
Environmental Conditions
Compressor Construction Fully sealed rotary type (inverter driven) Fully sealed rotary type (inverter driven)
Output kW 0.7 1.7 0.7 1.7
Condenser Fin and tube forced air cooling Double pipe water cooling
Heat Exchanger Construction Plate type heat exchanger Plate type heat exchanger
Material SUS316 grade stainless steel (brazing: copper) SUS316 grade stainless steel (brazing: copper)
Discharge Pump Construction Cascade type Cascade type
Output kW 0.25 0.4 0.75 0.4 0.75
Water tank capacity L approx. 15 approx. 20 approx. 15 approx. 20
Refrigerant R-410A R-410A
CE Marketing Built to Order -------------- Built To Order --------------
External Dimensions
(H × D × W)
mm G1 : 840 × 688 × 400
G2 : 927 × 688 × 400
G1 : 879 × 850 × 400
G2 : 966 × 850 × 400
G1 : 993 × 970 × 530
G2 : 1080 × 970 × 530
G1 : 879 × 850 × 400
G2 : 966 × 850 × 400
G1 : 993 × 970 × 530
G2 : 1080 × 970 × 530
Product mass (dry weight) kg G1 : 68
G2 : 73
G1 : 96
G2 : 100
G1 : 135
G2 : 140
G1 : 95
G2 : 98
G1 : 135
G2 : 140
Operating Noise Level (5) dB 55/57 56/60 62/64 55 59/60
  • 1. The air cooling machine is operated at a cold water temperature of 20 ° C, an ambient temperature of 32 ° C, a water cooling machine at a cold water temperature of 20 ° C, and a cooling water temperature at 32 ° C. The cooling capacity is 95% or more of the display capacity.
  • 2. The phase unbalance of power supply voltage should be within ±3%.
  • 3. Maximum operating current within the operating range.
  • 4. Except when starting and when the cooling load is small and the compressor is turned ON and OFF.
  • 5. The driving sound is 1 m front and 1 m high.
  • 6. It incorporates an overcurrent protection combined type earth leakage breaker as standard.
  • 1. Clean water and 30 to 40% industrial ethylene glycol solution are recommended for liquid (cold water) used in this machine. However, when using an industrial ethylene glycol aqueous solution of 30 to 40%, since the cooling capacity drops by about 10% Please be careful.
  • 2. Also, in the case of pure water, please set the electric conductivity to 1 S / cm or more.

Air cooling series Outline drawing

Water cooling series Outline drawing

Cooling capacity diagram

Inverter controllable lower limit heating amount Cold water: tap water

Pump characteristic curve chart

Amount of cooling water (for condensation)