ORION® Heavy Duty Air Cooled Chillers

Heavy Duty DC Inverter Chiller - Air Cooled Series

Bulit In Tank

Refrigeration Equipment

Models Air cooled
  • RKE3750B-V-G1 / G2 (with casters)
  • RKE5500B-V
  • RKE7500B-V
  • RKE11000B-V
  • RKE15000B-V

Specification Chart

Model

RKE 3750B-V G1/G2 (with casters)

RKE5500B-V RKE7500B-V RKE11000B-V RKE15000B-V
Performance Specification
Cooling capacity (1) kW 12.2 20.3 25.0 37.2 48.0
Heating capacity (2) kW 2.8 3.7 8.0 10.0
Operable ambient
temperature range
-20 to 45 (when using option - 20 to 50) -20 to 45
Operable fluid
temperature range
3 to 35 (0 to 35: when brine is used) (8)
Control accuracy (3) ± 0.1 ° C (± 2.0 ° C in energy saving mode setting)
Operating flow rate L / min 15 to 60 60 to 170 100 to 230
Power specifications
Power source (4) V (Hz) Three phase 200 ~ 220 ± 10% (50/60)
Power consumption (1) kW 5.4 9.8 10.2 14.4 18.1
Electric current (1) A 16.5 30.1 33.5 47.0 56.3
Power capacity (5) kVA 7.0 11.0 11.8 19.5 22.0
Breaker capacity (6) A 30 50 75 100
Operation control system Compressor speed control
Equipment details
Compressor Construction Totally sealed rotary type
(inverter driven)
All sealed type scroll type
(inverter driven)
output kW 1.7 3 4.6 7.46 11.19
Condenser Fin-and-tube type forced air cooling type
Heat Exchanger Construction Plate type heat exchanger
Material SUS 316 (brazing: Cu)
Discharge pump Construction Multistage swirl immersion type
output kW 1.1 (inverter driven) 2.0 (inverter driven) 2.5 (inverter drive) 3.7 (inverter driven)
Fan motor
output
output kW 0.4 (inverter driven) 0.75 (inverter driven) 0.4 × 2 (inverter driven)
Water tank capacity L About 60 About 90 About 100
Refrigerant R410A
Outside dimensions
(height × depth × width)
mm G 1: 1310
(G 2: 1536) × 752 × 720
1700 × 854 × 870 1700 × 854 × 1380 1800 × 854 × 1610
Unit mass(dry weight) kg G1: 200 · G2: 205 280 290 415 460
Operating noise level(50/60Hz)(7) dB 60 63 69 68
  • 1. Operating conditions: Chilled water temp.:20 °C, Cooling water temp.:32°C(water cooled units only), Ambient temp.: 32°C. Cooling capacity is atleast 95% of listed figures.
  • 2. Source voltage phase unbalance should be less than ±3%.
  • 3. The figure noted is when operating at the highest capacuty in the normal operating range.
  • 4. Continuous current load fluctuation with ±10%, and with stable ambient temp. and power supply, etc. Does not include starting times or when the cooling load is too small, in which case the compressor may cycle on and off.
  • 5. Operating nolse levels are from a position of 1m in front of the unit and at a height of 1m.
  • 6. Unit comes with a built-in multi-purpose overload and short circuit protection breaker.
  • 7. Use antifreeze when operating with fluid temperature settings of 0 to 3°C. (8), At time of startup only. Will differ depending on ambient temperature.
  • Note 1: The recommended liquid (chilled water) that can be used is either clean water or a 30 tp 40% ethylene glycol solution. Note that there will be a 10% reduction in cooling capacity if using a 30 to 40% ethylene glycol solution. Alternatively, if deionized water is to be used , it should have an electrical conductivity of at least 1 µS / cm.
  • Note 2: Heat output from the unit (in KW) is approx. 1.3times that of the cooling capacity.(Air cooled models)

Cooling Capacity Diagram : Air Cooled Model Cooling Power Comparison Diagram

External Dimensions : Air Cooled Model External Dimensions

Chilled Water Flow Chart

  • * The illustration shows the actual measured flow rate value when the bypass valve is closed.
  • * Flow rate changes based on inverter frequency
  • * The shaded area indicates the range possible for the adjusted frequency value.
  • * The flow rate and pressures indicated are those displayed on the chiller.