ORION ® RKL Series Chillers

Heavy duty, Air Cooled Chiller UNIT Cooler RKL Series

SUPER HEAVY DUTY CHILLERS

Refrigeration Equipment

Cooling capacity:14.1 KW - 48.0KW

Models Air cooled
  • RKL-2200-D
    • RKL-3750-D (Shown here)
  • RKL-5500-D
  • RKL-7500-D

Specification Chart

Air-cooled
RKL-2200-D RKL-3750-D RKL-5500-D RKL-7500-D
Performance
Specifications
Cooling capacity
50/60 Hz) (1),(2)
kW 7.9/8.5 11.6/12.2 18.7/20.3 25.0/27.1
Operating ambient
temp. range
°C 5 to 43
Operating temp. range
(fluid temp)
°C 5 to 30
Power
Specifications
Power Source V(Hz) Three phases 200± 10% (50/60), 220± 10% (60)
Power Comsumption
(50/60 Hz, 220 V) (2)
kW 3/4, 4 5 /6,6 7/8,8 10/12,12
Electric Current
(50/60 Hz, 220 V) (2)
A 11/13, 13 18/20, 20 24/27,27 33/37,37
Power capacity (3) kVA 5.5 8.3 11.8 18.7
Breaker capacity A 20 30 40 60
Environmental Conditions
compressor output kW 2.2 3.75 5.5 7.46
Condenser Fin-and-tube type forced air cooling
Heat
Exchanger
Construction Shell and coil
Material Shell: Polyethylene coil: SUS 304 grade stainless steel
Circulation pump
(50/60 Hz)
output W 150/180 400 750
Circulation amount L/min 40 to 60/40 to 70 70 to 115/70 to 130 80 to 120/80 to 140 110 to 140/110 to 175
Fan motor output (4) W 100 (inverter driven) 100 (inverter driven) 750 (inverter driven)
Refrigerant R-407C
Outside dimensions
(height × depth × width)
mm 1400 × 677 × 860 1445 × 705 × 1025 1740 × 815 × 1287
Unit mass (dry mass) kg About 200 About 270 About 600 About 650
Operating noise level
(50/60 Hz) (5)
dB 59/61 61/64 64/67 65/68
Required water tank capacity L Over 200 300 or more 450 or more 600 or more
* When operating at 1 liquid temperature 20 ° C, ambient temperature 32 ° C, cooling water temperature 32 ° C. The cooling capacity is 95% or more of the display capacity.
* 2 The phase balance between power supply voltages should be within ± 3%.
* 3 Maximum operating current within the operating range.
* 4 When the load is stable, it indicates that the state within the current load of ± 10% continues (except when the capacity control solenoid valve opens and closes). Setting change can be set by parameter F15 (initial value: high accuracy).
* 5 Driving sound is the front 1 m, height 1 m value.
* 6 Built-in overload protection combined type earth leakage breaker as standard.
Note 1) Please attach the attached Y type strainer (40 mesh) to the liquid inlet piping.
Note 2) For the liquid (cold water) used in this machine, fresh water and industrial ethylene glycol aqueous solution with a concentration of 30 to 40% are recommended.
However, when using an industrial ethylene glycol aqueous solution of 30 to 40%,
please note that the cooling capacity drops by about 10% .
Also, in the case of pure water, please set the electric conductivity to 1 ?S / cm or more.
Note 3) Apparatus exhaust heat quantity (kW) is about 1.3 times the cooling capacity. (Limited to air cooling)

Cooling Capacity

External Dimensions

Pump Characteristic Curves